Test Terminal Block
|
Rudolf Metering
Systems Test Terminal Blocks can be used for
testing a wide range of electrical equipment
including metering installations to facilitate
site-testing of polyphase meters and protective
relays, without disturbing the normal load
circuit. |
Product Information
Unique Features
• Gloss
black finished moulded bakelite
• Terminal
arrangements cover a wide range of applications
• Front
& back connected types
• All
terminals and screws are plated brass
• Moulded
insulation barriers between sets of terminals
• Link
facilities for testing purposes
Electrical Characteristics
Voltage insulation level: 600 volts
Current rating: 50 Amps
Case / Cover
Designed for projection mounting on switchboards or
panels, terminal blocks can be supplied with front or
back connection terminals. The cover is secured by two
knurled nuts which can be sealed to prevent unauthorised
access. Two detachable strips are fitted into the upper
and lower edges of the terminal cover. These strips can
be reversed to allow the cover to be in place during
tests.
Mounting
It is suitable for projection/surface mounting
Terminal Arrangement
The test terminal block is provided with 13 terminals
each with 6mm (1/4") diameter holes. It is consist
of 3 groups of current terminals and 4 voltage
terminals. Each group of current terminals shall consist
of 3 terminals with inter-terminal shorting links for
the short-circuiting of the current transformers
secondaries that are connected to the terminals. This is
necessary for the purpose of insertion of check meters
and for portable current injection test set. Connections
are possible from both ends of the terminals. Blanking
strips are provided to prevent unauthorised entry to the
terminals when the cover is sealed.
Phase Barriers
Each terminal shall be separated by phase barriers,
moulded integrally with the base of the terminal block.
The voltage terminal is shrouded in moulded bakelite.
Terminals and Back Stems
The terminals are made of plated brass and is fitted
with plated brass back stems of 50mm to 60mm in length
and 6mm (OBA) in diameter except for terminal numbers 10
and 12 (viewed from the front) which are 20mm longer
than the rest. The stems are insulated and suitably
spaced to facilitate connections. The length of
insulation shall cover only the unthreaded portion of
the back stem leaving the threaded portion exposed. Each
stem are provided with two plated brass nuts, two plated
brass washers and a spring washer. The assembly of brass
nuts shall be placed just above the unthreaded portion
of the back stem.
|