Power Quality Analyzer - PQA1 44

The PQA-1 44 is an
instrument that can be used as a Power Quality Analyzer
to support any network connection configuration, such as
3 and 4 Wire, Wye and Delta, and single-phase. The
connection is either direct (up to 347/600 VAC) or using
a Potential Transformer (PT). Minimum burden on the
Current Transformers (CTs) is achieved by connecting the
(CTs) without a physical contact. Delta networks use 2
or 3 CTs and Wye networks use 3 or 4 CTs.
When
the system is configured as a Delta network, it displays
the L-to-L current and power, in additional to the line
currents and total power. The system measures the line
current from the CTs and calculates the current and
power inside the feeder transformer (or generator). In
completely balanced networks, the internal currents are
1/Φ 3 of the line currents. In many cases,, the network
is not balanced and the internal currents are different
from these expected.
Basic Features
Metered Values
True RMS measurements
Ultra rapid. real-time, cycle by cycle
measurements, at 128 samples per cycle. Real-time values
over 8 through 256 cycles for easy reading
Choice of models ranging from essential
measurements only (Volts, currents, frequency and
powers) to over 2000 electrical parameters
Mm/Max values
Four quadrant readings (power, power factor)
Displays neutral voltage and current
Time-of-Use (TOU)
Time-of-Use information is automatically stored
for each predefined period
PowerlQ software calculates electricity costs
according to varying tariffs (based on time, season
etc.)
Power Quality
Waveform display and capturing, at 128 samples
per cycle
Harmonics analysis, up to 63rd harmonic
(individual, THD, K and crest factors)
Sag/Swell recording (magnitude, duration and
trigger events)
Compliance Monitoring
Compliance monitoring of international power
quality standards
These monitoring operate on all product series
(e.g. the harmonics level is tested even if the
meter doesnt include harmonics display)
Logging & Recording
Up to
2048KB of flash memory
High speed data recording for short duration
critical events
Logging ol over 2000 parameters at scheduled
intervals or by set-points
Mm/Max recording of key parameters
Logging of setup changes, set-point and power
quality events
Precise timestamp synchronized to external GPS
(optional)
Input, Output & Relays
On hoard relay can be controlled automatically by
internal set-points
Optional 4 digital inputs and 2 outputs for
multiple purposes, such as synchronization to utility
meter or to generate energy pulsing (Wh, VArh and VAh)
Graphic Display & User Interface
Extra large graphic I CD screen
High visibility (FSTN technology)
Bright Backlight
characters are displayed in varying sizes to
enhance visibility from long distances
The user interface offers an easy to use,
installation and configuration menu driven operation
Communication
Optional RS-485 or RS-232 communication port
Supported protocol: ElCom protocol - Rudolfs
unique ultra rapid communication protocol and ModBus RTU
Baud rate of up to 115200 BPS
Fully automated baud rate setup
Structure
Allows easy adaptation of the unit to current and
future requirements
Easy upgrading of the firmwave (internal
software)
Network Types
Supports any network connection configuration (3
and 4 Wire, Wye arid Delta, single-phase etc.)
Feeder transformer (or local generator) current
and power analysis (see Applications section)
Unique dual load model enables simultaneous
analysis of two loads such as parallel-connected
transformers, or mains plus additional load (e.g., large
motor, welder, capacitor bank)
Software
User-friendly PC software (PowerIQ)
Includes on-line help for easy use.
|